Skip to content

This repository shows how the serial interface of the CC100 can be integrated into a Docker container (Node-RED)

Notifications You must be signed in to change notification settings

WAGO/cc100-serial-communication

Folders and files

NameName
Last commit message
Last commit date

Latest commit

 

History

9 Commits
 
 
 
 
 
 

Repository files navigation

cc100-serial-communication

This repository shows how the serial interface of the CC100 can be integrated into a Docker container (Node-RED). For this purpose, the WAGO Energy Meter (MID) is connected as an example. The communication between Node-RED and the MID is based on Modbus RTU.

Concept of serial communication with the CC100

Prerequisites

  • WAGO CC100 (751-9301) => !!! please use Firmware 23 !!!
  • WAGO Energy Meter (MID) (e.g. 879-3000)
  • for firmware download or update see cc100-firmware
  • PC with preinstalled SSH Client (e.g. PuTTY)
  • Web browser of your choice. (e.g. chrome)

Setup

Connect the terminals X11.1 and X11.2 of the CC100 with the terminals 7 and 8 of the MID

Connection of the CC100 with the MID

CC100 Login

Start SSH Client e.g. Putty

login as 'root'
password 'wago'

Check docker installation

docker info
docker ps           # to see all running containers (no container should run)
docker images       # to see all preinstalled images

Integration of the serial interface into the Node-RED container

docker run -d \
--name node-red \
--restart always \
--privileged=true \
--user=root \
-p 1880:1880 \
-v node_red_user_data:/data \
-v /dev/ttySTM1:/dev/serial \
wagoautomation/node-red-cc100:1.0.0

The serial interface of the CC100 is located on /dev/ttySTM1. By bind-mounting this interface, the Node-RED container gains access to it. In this case /dev/ttySTM1 is replicated to the /dev/serial directory. /dev/serial is created when the container is started. The directory for the volume mount is basically arbitrary, the path must only be passed correctly to Node-RED in the following steps.

Read MID data via Modbus RTU

  1. Open Node-RED by typing <ip of your CC100>:1880 into your browser
  2. Drag and drop the Modbus Read node into your flow

Modbus Read Node

  1. Configure the node as follows

Edit Modbus Read Node

In this case the voltage of phase L1 is read out as an example. The address is taken from the data sheet of the MID and converted into a decimal value. The Quantity is two because the value is stored in two registers.

  1. Configure the MID as a new Modbus slave by clicking on the pencil and making the following settings

Configuration MID as Modbus Slave

For Serial Port, enter the path that leads to the directory that was replicated with the Node-RED start command. The information about the Baud rate, the Data bits, the Stop bits and the Parity was taken from the data sheet of the MID.

  1. Connect a debug node to the first output of the modbus read node

Node-RED Flow Read Raw MID Data

  1. Deploy the flow
  2. Open the debug console

Debug Console Raw Data

You can adapt the flow to your needs by reading other registers as well. The addresses of all registers that can be read can be found in the data sheet of the MID. Please note that the addresses for the Modbus read nodes must be specified as decimal values.

Interpret MID data

  1. Install the node-red-contrib-buffer-parser lib
  2. Use the buffer parser node to adjust your flow as follows

Connect buffer parser node

  1. Edit the node as follows

Edit Buffer Parser Node

The data sheet of the MID shows that the voltage L1 has the data type Float ABCD (Big Endian). Accordingly select the data type float(be).

  1. Add another debug node

Node-RED Flow Read MID Data

  1. Deploy the flow
  2. Open the debug console

Debug Console Interpreted Data

Node-RED flow

You can also import the flow shown above directly. Make sure that the replicated path for the serial port in the Node-RED start command matches the serial port of the Modbus slave in the Modbus Read node.

[
    {
        "id": "2a30359f7d24ebbc",
        "type": "modbus-read",
        "z": "29a2155a87f7168d",
        "name": "Read Voltage L1",
        "topic": "",
        "showStatusActivities": false,
        "logIOActivities": false,
        "showErrors": false,
        "unitid": "",
        "dataType": "HoldingRegister",
        "adr": "20482",
        "quantity": "2",
        "rate": "5",
        "rateUnit": "s",
        "delayOnStart": false,
        "startDelayTime": "",
        "server": "f916ff91cd483ac8",
        "useIOFile": false,
        "ioFile": "",
        "useIOForPayload": false,
        "emptyMsgOnFail": false,
        "x": 180,
        "y": 100,
        "wires": [
            [
                "32398913de4d8fcc",
                "72f25637663dce9b"
            ],
            []
        ]
    },
    {
        "id": "72f25637663dce9b",
        "type": "buffer-parser",
        "z": "29a2155a87f7168d",
        "name": "parse FLOAT ABCD",
        "data": "payload",
        "dataType": "msg",
        "specification": "spec",
        "specificationType": "ui",
        "items": [
            {
                "type": "floatbe",
                "name": "voltage L1",
                "offset": 0,
                "length": 1,
                "offsetbit": 0,
                "scale": "1",
                "mask": ""
            }
        ],
        "swap1": "",
        "swap2": "",
        "swap3": "",
        "swap1Type": "swap",
        "swap2Type": "swap",
        "swap3Type": "swap",
        "msgProperty": "payload",
        "msgPropertyType": "str",
        "resultType": "keyvalue",
        "resultTypeType": "return",
        "multipleResult": false,
        "fanOutMultipleResult": false,
        "setTopic": true,
        "outputs": 1,
        "x": 420,
        "y": 100,
        "wires": [
            [
                "85780372fbcf8928"
            ]
        ]
    },
    {
        "id": "85780372fbcf8928",
        "type": "debug",
        "z": "29a2155a87f7168d",
        "name": "output voltage L1",
        "active": true,
        "tosidebar": true,
        "console": false,
        "tostatus": false,
        "complete": "payload",
        "targetType": "msg",
        "statusVal": "",
        "statusType": "auto",
        "x": 670,
        "y": 100,
        "wires": []
    },
    {
        "id": "32398913de4d8fcc",
        "type": "debug",
        "z": "29a2155a87f7168d",
        "name": "raw data",
        "active": true,
        "tosidebar": true,
        "console": false,
        "tostatus": false,
        "complete": "payload",
        "targetType": "msg",
        "statusVal": "",
        "statusType": "auto",
        "x": 380,
        "y": 60,
        "wires": []
    },
    {
        "id": "f916ff91cd483ac8",
        "type": "modbus-client",
        "name": "MID",
        "clienttype": "serial",
        "bufferCommands": true,
        "stateLogEnabled": false,
        "queueLogEnabled": false,
        "failureLogEnabled": true,
        "tcpHost": "192.168.178.68",
        "tcpPort": "502",
        "tcpType": "DEFAULT",
        "serialPort": "/dev/serial",
        "serialType": "RTU-BUFFERD",
        "serialBaudrate": "9600",
        "serialDatabits": "8",
        "serialStopbits": "1",
        "serialParity": "even",
        "serialConnectionDelay": "100",
        "serialAsciiResponseStartDelimiter": "0x3A",
        "unit_id": "1",
        "commandDelay": "1",
        "clientTimeout": "1000",
        "reconnectOnTimeout": true,
        "reconnectTimeout": "2000",
        "parallelUnitIdsAllowed": true
    }
]

Further CC100 projects

Sources

About

This repository shows how the serial interface of the CC100 can be integrated into a Docker container (Node-RED)

Resources

Stars

Watchers

Forks

Releases

No releases published

Packages