@@ -0,0 +1,211 @@
within Buildings.Controls.OBC.ASHRAE.PrimarySystem.ChilledBeamSystem.SecondaryPumps.Subsequences;
block ChangeStatus
"Sequence to change pump status"

parameter Integer nPum = 2
"Total number of pumps";

Buildings.Controls.OBC.CDL.Interfaces.BooleanInput uChiWatPum[nPum]
"Chilled water pump status"
annotation (Placement(transformation(extent={{-140,-20},{-100,20}})));

Buildings.Controls.OBC.CDL.Interfaces.BooleanInput uNexLagPumSta
"Status of next lag pump"
annotation (Placement(transformation(extent={{-140,60},{-100,100}})));

Buildings.Controls.OBC.CDL.Interfaces.BooleanInput uLasLagPumSta
"Status of last lag pump"
annotation (Placement(transformation(extent={{-140,30},{-100,70}})));

Buildings.Controls.OBC.CDL.Interfaces.IntegerInput uNexLagPum
"Index of next lag pump"
annotation (Placement(transformation(extent={{-140,-60},{-100,-20}})));

Buildings.Controls.OBC.CDL.Interfaces.IntegerInput uLasLagPum
"Index of last lag pump"
annotation (Placement(transformation(extent={{-140,-100},{-100,-60}})));

Buildings.Controls.OBC.CDL.Interfaces.BooleanOutput yChiWatPum[nPum]
"Chilled water pump status"
annotation (Placement(transformation(extent={{100,-20},{140,20}})));

protected
parameter Integer pumInd[nPum]={i for i in 1:nPum}
"Pump index, {1,2,...,n}";

Buildings.Controls.OBC.CDL.Routing.BooleanScalarReplicator booRep1(
final nout=nPum)
"Replicate boolean input"
annotation (Placement(transformation(extent={{-80,70},{-60,90}})));

Buildings.Controls.OBC.CDL.Routing.BooleanScalarReplicator booRep2(
final nout=nPum)
"Replicate boolean input"
annotation (Placement(transformation(extent={{-80,40},{-60,60}})));

Buildings.Controls.OBC.CDL.Integers.Equal intEqu2[nPum]
"Check next lag pump"
annotation (Placement(transformation(extent={{-60,-50},{-40,-30}})));

Buildings.Controls.OBC.CDL.Integers.Equal intEqu3[nPum]
"Check last lag pump"
annotation (Placement(transformation(extent={{-60,-90},{-40,-70}})));

Buildings.Controls.OBC.CDL.Logical.LogicalSwitch nexLagPumSta[nPum]
"Next lag pump status"
annotation (Placement(transformation(extent={{-20,-50},{0,-30}})));

Buildings.Controls.OBC.CDL.Logical.LogicalSwitch lasLagPumSta[nPum]
"Last lag pump status"
annotation (Placement(transformation(extent={{-20,-90},{0,-70}})));

Buildings.Controls.OBC.CDL.Logical.Or enaPum[nPum]
"Chilled water pump status"
annotation (Placement(transformation(extent={{10,-50},{30,-30}})));

Buildings.Controls.OBC.CDL.Logical.And pumSta[nPum]
"Chilled water pump status"
annotation (Placement(transformation(extent={{20,-90},{40,-70}})));

Buildings.Controls.OBC.CDL.Logical.LogicalSwitch remPum[nPum]
"Remove pump"
annotation (Placement(transformation(extent={{50,-70},{70,-50}})));

Buildings.Controls.OBC.CDL.Logical.LogicalSwitch addPum[nPum]
"Add pump"
annotation (Placement(transformation(extent={{60,-10},{80,10}})));

Buildings.Controls.OBC.CDL.Routing.IntegerScalarReplicator intRep(
final nout=nPum)
"Integer replicator"
annotation (Placement(transformation(extent={{-90,-50},{-70,-30}})));

Buildings.Controls.OBC.CDL.Routing.IntegerScalarReplicator intRep1(
final nout=nPum)
"Integer replicator"
annotation (Placement(transformation(extent={{-90,-90},{-70,-70}})));

Buildings.Controls.OBC.CDL.Integers.Sources.Constant conInt[nPum](
final k=pumInd)
"Pump index"
annotation (Placement(transformation(extent={{-90,10},{-70,30}})));

equation
connect(nexLagPumSta.u2, intEqu2.y)
annotation (Line(points={{-22,-40},{-38,-40}}, color={255,0,255}));

connect(intEqu3.y, lasLagPumSta.u2)
annotation (Line(points={{-38,-80},{-22,-80}}, color={255,0,255}));

connect(uNexLagPumSta, booRep1.u)
annotation (Line(points={{-120,80},{-82,80}}, color={255,0,255}));

connect(uLasLagPumSta, booRep2.u)
annotation (Line(points={{-120,50},{-82,50}}, color={255,0,255}));

connect(intRep.y, intEqu2.u1)
annotation (Line(points={{-68,-40},{-62,-40}}, color={255,127,0}));

connect(intRep1.y, intEqu3.u1)
annotation (Line(points={{-68,-80},{-62,-80}}, color={255,127,0}));

connect(uNexLagPum, intRep.u)
annotation (Line(points={{-120,-40},{-92,-40}}, color={255,127,0}));

connect(uLasLagPum, intRep1.u)
annotation (Line(points={{-120,-80},{-92,-80}}, color={255,127,0}));

connect(booRep2.y, lasLagPumSta.u1) annotation (Line(points={{-58,50},{-36,50},
{-36,-72},{-22,-72}}, color={255,0,255}));

connect(booRep1.y, nexLagPumSta.u1) annotation (Line(points={{-58,80},{-24,80},
{-24,-32},{-22,-32}}, color={255,0,255}));

connect(uChiWatPum, nexLagPumSta.u3) annotation (Line(points={{-120,0},{-30,0},
{-30,-48},{-22,-48}}, color={255,0,255}));

connect(uChiWatPum, lasLagPumSta.u3) annotation (Line(points={{-120,0},{-30,0},
{-30,-88},{-22,-88}}, color={255,0,255}));

connect(nexLagPumSta.y, enaPum.u1)
annotation (Line(points={{2,-40},{8,-40}}, color={255,0,255}));

connect(uChiWatPum, enaPum.u2) annotation (Line(points={{-120,0},{4,0},{4,-48},
{8,-48}}, color={255,0,255}));

connect(uChiWatPum, remPum.u1) annotation (Line(points={{-120,0},{4,0},{4,-52},
{48,-52}}, color={255,0,255}));

connect(enaPum.y, addPum.u1) annotation (Line(points={{32,-40},{40,-40},{40,8},
{58,8}}, color={255,0,255}));

connect(lasLagPumSta.y, pumSta.u1)
annotation (Line(points={{2,-80},{18,-80}}, color={255,0,255}));

connect(enaPum.y, pumSta.u2) annotation (Line(points={{32,-40},{40,-40},{40,
-56},{10,-56},{10,-88},{18,-88}},
color={255,0,255}));

connect(pumSta.y, remPum.u3) annotation (Line(points={{42,-80},{46,-80},{46,-68},
{48,-68}}, color={255,0,255}));

connect(booRep2.y, remPum.u2) annotation (Line(points={{-58,50},{-36,50},{-36,
-60},{48,-60}}, color={255,0,255}));

connect(booRep1.y, addPum.u2) annotation (Line(points={{-58,80},{50,80},{50,0},
{58,0}}, color={255,0,255}));

connect(remPum.y, addPum.u3) annotation (Line(points={{72,-60},{80,-60},{80,-40},
{50,-40},{50,-8},{58,-8}}, color={255,0,255}));

connect(addPum.y,yChiWatPum) annotation (Line(points={{82,0},{120,0}},
color={255,0,255}));

connect(conInt.y, intEqu2.u2) annotation (Line(points={{-68,20},{-66,20},{-66,
-48},{-62,-48}}, color={255,127,0}));

connect(conInt.y, intEqu3.u2) annotation (Line(points={{-68,20},{-66,20},{-66,
-88},{-62,-88}}, color={255,127,0}));

annotation (
defaultComponentName="chaSta",
Icon(coordinateSystem(preserveAspectRatio=false,
extent={{-100,-100},{120,100}}),
graphics={
Rectangle(
extent={{-100,-100},{100,100}},
lineColor={0,0,127},
fillColor={255,255,255},
fillPattern=FillPattern.Solid),
Text(
extent={{-100,150},{100,110}},
lineColor={0,0,255},
textString="%name")}),
Diagram(coordinateSystem(preserveAspectRatio=false, extent={{-100,-100},{100,100}})),
Documentation(info="<html>
<p>
Block that changes the status of pumps.
</p>
<p>
<ol>
<li>
When the block receives the index of next lag pump to be enabled <code>uNexLagPum</code>
and a <code>true</code> pulse on the next lag pump status <code>uNexLagPumSta</code>,
it changes the pump status <code>yHotWatPum[uNexLagPum]</code> to <code>true</code>.
</li>
<li>
When the block receives the index of last lag pump to be disabled <code>uLasLagPum</code>
and a <code>false</code> pulse on the last lag pump status <code>uLasLagPumSta</code>, it changes
the pump status <code>yHotWatPum[uLasLagPum]</code> to <code>false</code>.
</li>
</ol>
</p>
</html>", revisions="<html>
<ul>
<li>
August 19, 2020, by Karthik Devaprasad:<br/>
First implementation.
</li>
</ul>
</html>"));
end ChangeStatus;