dbus-modbus-client

Reads data from Modbus devices and publishes on D-Bus. Service names and paths are per the Victron D-Bus specification.

Modbus devices using the RTU, TCP, and UDP transports are supported.

VregLink

With some devices, the VregLink interface is supported.

The VregLink interface uses a block of up to 125 Modbus holding registers accessed with the Modbus Read/Write Multiple Registers function (code 23). Byte data is packed into 16-bit register values MSB first. All accesses start from offset zero in the VregLink block. The base address is device specific.

Write

Offset Field
0 VREG ID
1 Size
2..N Data

A write operation contains the VREG to access and, optionally, data for setting the value. The size field indicates the length in bytes of the data and must be 2x the number of registers or 1 less. To select a VREG for a subsequent read, only the first field (VREG ID) should be present.

Read

Offset Field
0 VREG ID
1 Status
2 Size
3..N Data

A read operation returns the value of the selected VREG or an error code if the access failed. The size field indicates the length of the data in bytes. The actual size of the VREG value is returned even if the requested number of registers is too small to contain it.

Status

The following status codes are possible.

Value Meaning
0 Success
0x8000 Read: unknown error
0x8001 Read: VREG does not exist
0x8002 Read: VREG is write-only
0x8100 Write: unknown error
0x8101 Write: VREG does not exist
0x8102 Write: VREG is read-only
0x8104 Write: data invalid for VREG

Examples

If the VregLink register block begins at address 0x4000, then to read VREG 0x100 (product ID), the following Modbus transaction would be used.

Field Name Hex Comment
Request
Function 17 Read/Write Multiple Registers
Read Starting Address Hi 40 VregLink base address
Read Starting Address Lo 00
Quantity to Read Hi 00
Quantity to Read Lo 05
Write Starting Address Hi 40 VregLink base address
Write Starting address Lo 00
Quantity to Write Hi 00
Quantity to Write Lo 01
Write Byte Count 02
Write Register Hi 01 PRODUCT_ID
Write Register Lo 00
Response
Function 17 Read/Write Multiple Registers
Byte Count 0A
Read Register Hi 01 PRODUCT_ID
Read Register Lo 00
Read Register Hi 00 Status: success
Read Register Lo 00
Read Register Hi 00 Size: 4
Read Register Lo 04
Read Register Hi 00 Product ID
Read Register Lo 12
Read Register Hi 34
Read Register Lo FE

To set VREG 0x10C (description), the Modbus transaction might look as follows.

Field Name Hex Comment
Request
Function 17 Read/Write Multiple Registers
Read Starting Address Hi 40 VregLink base address
Read Starting Address Lo 00
Quantity to Read Hi 00
Quantity to Read Lo 02
Write Starting Address Hi 40 VregLink base address
Write Starting address Lo 00
Quantity to Write Hi 00
Quantity to Write Lo 08
Write Byte Count 10
Write Register Hi 01 DESCRIPTION1
Write Register Lo 0C
Write Register Hi 00 Size: 11
Write Register Lo 0B
Write Register Hi 4D 'M'
Write Register Lo 79 'y'
Write Register Hi 20 ' '
Write Register Lo 50 'P'
Write Register Hi 72 'r'
Write Register Lo 65 'e'
Write Register Hi 63 'c'
Write Register Lo 69 'i'
Write Register Hi 6f 'o'
Write Register Lo 75 'u'
Write Register Hi 73 's'
Write Register Lo 00 Padding
Response
Function 17 Read/Write Multiple Registers
Byte Count 04
Read Register Hi 01 DESCRIPTION1
Read Register Lo 0C
Read Register Hi 00 Status: success
Read Register Lo 00